27kV/100A, 38kV/100A, 27kV/200A

Overview:
Used in overhead electrical power distribution lines to provide overcurrent protection and visible indication when a fault occurs. Meets the requirements of ANSI / IEEE C37.40/41/42 and IEC60282-2:2008. The expulsion fuse cutouts that we offer are prepared to be installed on the poles of the medium voltage networks of the electric distribution systems. They are prepared for a continuous use regime, withstanding the thermal, dynamic and electrical stresses caused by short circuits and over voltages, as well as to effectively cut short-circuit currents, from the minimum melting current to the maximum that may appear in the worst case under the specified condition


Product Detail

Product Tags

Specifications

Product Type

 

EXPULSION FUSE CUT OUT, 27 kV, 150kVBIL, 100 A 8/12kA, 470mm CREEPAGE DISTANCE

EXPULSION FUSE CUT OUT, 38kV, 170kVBIL, 100A, 5/8 kA, 660mm CREEPAGE DISTANCE

EXPULSION FUSE CUTOUT, 27kV, 150kVBIL, 200A, 7.1/10 kA, 432mm CREEPAGE DISTANCE

No.

Features

Unit

Value

Value

Value

1

BASE

 

Model

HV1-27/100-8

 HV1-38/100-5

HV1-27/200-7.1

Standard

ANSI/IEEE C 37.40/41/42

 IEC60282- 2:2008

ANSI C-37.40/41/42 and IEC60282-2

ANSI/IEEE  C37.40/41/42 y IEC60282-2:2008

Rated Current

A

100

100

200

Rated Voltage

kV

27

38

27

Minimum Short Circuit Current
- Symmetrical

kA

8

5

7.1

- Asymmetrical

kA

12

8

10

Minimum isolation level:
- Impulse withstand voltage (BIL), phase to ground and between phases.

kV

150

170

150

- Withstand voltage at power frequency between phases, dry, 1 min.

kV

60

80

60

- Withstand voltage at power frequency between phase and ground, in wet, 10s.

kV

50

70

50

Insulating porcelain material of the base with high purity alumina compositions (between 94% to 99%) with the addition of vitrifiers.

Yes

Yes

Yes

Minimum creepage distance (Phase-Earth)

mm

470

660

432

Contact Material

Silver electrolytic copper

Silver electrolytic copper

Silver electrolytic copper

- Minimum thickness of the top contact silver layer (tab)

µm

15

15

15

- Maximum electrical contact resistance between each terminal and the nearest metal part accessible after contact

Ohm

0.000099

0.000099

0.000099

- Upper contact pressure spring with fastening and alignment mechanism

Stainless steel, grade 304 according to AISI 304, DIN 1.4301

Stainless steel, grade 304 according to AISI 304, DIN 1.4301

Stainless steel according to  AISI 304, DIN 1.4301

Terminals material

Tinned copper

Tinned copper

Tinned copper

-Conductor Range (Diameter)

mm

4.11-11.35

4.11-11.35

4.11-11.35

-Terminals for use with copper or aluminum conductors

Yes

Yes

Yes

-Type of terminals

Parallel slots, must include bolt, nuts and pressure washers made of stainless steel

Parallel slots, must include bolt, nuts and pressure washers made of stainless steel

Parallel slots, must include bolt, nuts and pressure washers made of stainless steel

Top support channel material

Galvanized structural steel

Galvanized structural steel

Galvanized structural steel

- Galvanized Material Standard

ASTM A575

ASTM A575

ASTM A575

- Galvanizing Standard

ASTM A153

ASTM A153

ASTM A153

- Minimum average thickness

µm

86

86

86

Minimum opening angle

120°

120°

120°

Minimum number of mechanical operations guaranteed

No.

200

200

200

Minimum mechanical resistance of the horn for load operation

daN

200

200

200

Dimensions (See Figure 1)
L

mm

 704

842

 704

M

mm

 409

 431

 409

N

mm

 476

 567

 476

P

mm

72

 82

 72

Q

mm

131

 147

 131

2

FUSE HOLDER TUBE
Features
- Standard

ANSI/IEEE C 37.40/41/42

ANSI/IEEE C 37.40/41/42

ANSI/IEEE C 37.40/41/42

- Rated voltage

kV

27

38

27

- Rated current

A

100

100

200

- Minimum symmetrical/asymmetrical short-circuit current

kA

8/12

5/8

7.1/10

- Internal diameter range
- minimum

mm

11.1

11.1

17.5

- maximum

mm

18

18

23

- Length (allowable range)

mm

375±3

466±3

375±3

- Metal parts of joining with the base

Cast Bronze

Cast Bronze

Cast Bronze

- Fuse holder tube cover (top contact)

Silver electrolytic copper, with a minimum thickness of 8 um

Silver electrolytic copper, with a minimum thickness of 8 µm

Silver electrolytic copper, with a minimum thickness of 8 µm

- Eye hook for pole operation

Cast Bronze, with minimum mechanical resistance of 200daN

Cast Bronze, with minimum mechanical resistance of 200daN

Cast Bronze, with minimum mechanical resistance of 200daN

- Fuse holder tube material.

Fiberglass with internal coating in moisture-proof vulcanized fiber

Fiberglass with internal coating in moisture-proof vulcanized fiber

Fiberglass with internal coating in moisture-proof vulcanized fiber

- Fuse holder opening and closing mechanism (fuse holder base)

to avoid fuse holder tube un-alignment greater than 15mm

to avoid holder tube un-alignment no more than 15mm

to avoid fuse holder tube un-alignment no more than 15mm
Suitable for chicote fuses with removable head (Arc shortening rod)

Yes

Yes

Yes

3

FIXING ACCESSORIES
- Type of fixation

Type B, according to ANSI/IEEE C37.42

Type B, according to ANSI/IEEE C37.42

Type B, according to ANSI/IEEE C37.42

- Material

Galvanized Steel

Galvanized Steel

Galvanized Steel

- Material standard

ASTM A575

ASTM A575

ASTM A575

- Galvanizing Standard

ASTM A153

ASTM A153

ASTM A153

- Minimum average thickness

µm

86

86

86