Highlight
MODULAR DESIGN
SML PROTOCOL
TIME OF USE
HIGH PROTECTION DEGREE
Specifications
Item | Parameter |
Basic Parameter | Active accuracy:Class A (EN50470-1-3) or Class 2 (IEC62053-21) |
Rated voltage:230V | |
Specified operation range:0.7Un~1.2Un | |
Rated current:5(60)A | |
Starting current:0.004Ib | |
Frequency:50/60Hz | |
Pulse constant:1000 imp/kWh (configurable) | |
Current circuit power consumption≤4VA | |
Voltage circuit power consumption≤2W/10VA | |
Operating temperature range:-40°C ~ +80°C | |
Storage temperature range:-40°C ~ +85°C | |
Type Testing | IEC 62052-11 IEC 62053-21 EN 50470-1-3 |
Communication | Optical port “INFO interface” |
RS485 “MSB interface” | |
SML 1.04
One way and two way communication |
|
Measurement | One element |
Import active energy
Export active energy |
|
Instantaneous:Voltage,Current,Active power,Frequency | |
LED&LCD Display | LED indicator:Active pulse |
LCD energy display:6+0;Historical power display:5+1 | |
LCD display mode:Button display,Automatic display,Power-off display
Display time and content is configurable |
|
Tariff Management | 2 tariff
Apply voltage to the tariff terminal,or send a switch tariff command to achieve tariff switching |
Storage | NVM,at least 15 years |
Mechanical | Installation:DIN Standard |
Enclosure protection:IP54 | |
Support installation of seals | |
Meter Case:Polycarbonate | |
Dimensions (L*W*H):239.6mm*130mm*49.3mm | |
Weight:Approx. 0.62kg | |
Connection wiring Cross-sectional area:2.5-16mm² | |
Connection type:LLN |
Write your message here and send it to us