Hot Product
banner

PRODUCTS

PIN type Polymeric Insulator

Type:
13.8 kV / 22.9 kV

Overview:
Pin type Polymeric Insulators are made of the highest quality materials. The core is made of fiberglass with Fiberglass Round Rod type ECR and the insulating material of housing and sheds of high consistency silicone rubber.
They are designed and manufactured to be installed as supports for overhead lines, suitable to withstand the stresses from the weight and strength of the conductors and the metallic accessories that hold the conductors, to withstand the action of the wind on them and on the elements they support. They withstand the thermal, dynamic and electrical stresses from possible short circuits, maximum operating voltage and over voltages.



Product Detail

Product Tags

Specifications

Features

Unit

VALUE

VALUE

PIN TYPE POLYMERIC INSULATOR 13.8 kV

PIN TYPE POLYMERIC INSULATOR 22.9 kV

1

Operating Voltage(Phase-Phase)

≤ 13.8 kV

≥13.8 kV , ≤22.9 kV

2

Insulator model

FPQ-24kV/12kN

FPQ-35kV/12kN

3

Standard

IEC 61952:2008

IEC 61952:2008

4

Design and construction features
Core material (core)

Fiberglass with Fiberglas Round Rod Bar ECR

Fiberglass with Fiberglas Round Rod Bar ECR

Insulated housing and sheds:

High consistency silicone rubber type HTV or LSR

High consistency silicone rubber type HTV or LSR

- Resistance to tracking and erosion of insulating material: Silicone rubber

Class 2A, 6 kV (according to IEC 60587)

Class 2A, 6 kV (according to IEC 60587)

Material of the coupling hardware

Forged steel

Forged steel

Insulator Head Material

Porcelain

Porcelain

Galvanization of hardware

According to ASTM A153/A153M, average thickness of 86um

According to ASTM A153/A153M, average thickness of 86um

5

Electrical Values:
Operation voltage phase-phase

kV

10kV , 13.2kV to 13.8kV

13.8kV to 22.9kV

Maximum voltage for the insulator Um

kV(r.m.s)

24

35

Nominal frequency

Hz

60

60

Minimum creepage distance

mm

645

915

Arcing Distance

mm

230

275

Sheds diameter

mm

130/110

130/110

Sheds passage

mm

22.5

22.5

Withstand voltage at the industrial frequency:
-Dry

kV

80

115

-Wet

kV

70

105

Impulse Withstand voltage 1.2/50us:
-Positive

kV

150

190

-Negative

kV

200

220

Low Frequency Test Voltage (RMS to Earth)

kV

22

30

RIV Maximum at 1000 KHz

Microvolts

100

100

6

Mechanical values:
Minimal cantilever strength

kN

12

12

Compression effort

kN

≥ 8

45

Weight

kg

4.3

≥8

Core diameter

mm

45

4.6

Minimum PIN height

mm

237

130

Diameter of bolt

mm

20

42

7

Design tests

According to clause 10 IEC61952

According to clause 10 IEC61952

8

Type tests

According to clause 11 IEC61952

According to clause 11 IEC61952

9

Sampling tests

According to clause 12     IEC 61952

According to clause 12 IEC61952

10

Individual tests

According to clause 13     IEC 61952

According to clause 13 IEC61952

11

UV resistance tests

According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3

According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3

12

Includes spike

Yes

Yes