OEM Famous Self-supporting cable Pricelist – Suspension type Polymeric Insulator – Holley Detail:
Specifications
|
Products Type |
|
SUSPENSION TYPE POLYMERIC INSULATOR 13.8 kV |
SUSPENSION TYPE POLYMERIC INSULATOR 22.9 kV |
|
Features |
Unit |
Value |
Value |
1 |
Operating voltage (Phase – Phase) |
|
≤ 13.8 kV |
≥13.8 kV , ≤22.9 kV |
2 |
Designation, model |
FXB-24kV/70kN |
FXB-36kV/70kN |
|
3 |
Standards |
IEC 61109:2008, ANSI C29.13 |
IEC 61109:2008, ANSI C29.13 |
|
4 |
Manufacturing Features | |||
Core material |
Fiberglass with Fiberglas Round Rod Bar ECR |
Fiberglass with Fiberglas Round Rod Bar ECR |
||
Insulated housing and sheds: |
High consistency silicone rubber type HTV or LSR |
High consistency silicone rubber type HTV or LSR |
||
- Resistance to tracking and erosion of insulating material: Silicone rubber |
Class 2A, 6kV (according to ASTM D2303 – IEC 60587) |
Class 2A, 6kV (according to ASTM D2303 – IEC 60587) |
||
Material of the coupling hardware |
Forged steel |
Forged steel |
||
Galvanization of hardware |
According to ASTM A153/A153M, average thickness of 86µm |
According to ASTM A153/A153M, average thickness of 86µm |
||
Types of coupling |
Clevis – Tongue, |
Clevis – Tongue |
||
Key |
Stainless steel |
Stainless steel |
||
5 |
Electrical Values: | |||
Operation voltage phase-phase |
kV |
10 kV, 13.2 kV to 13.8 kV |
13.8 kV to 22.9 kV |
|
Maximum voltage for the insulator Um |
kV(r.m.s) |
24 |
36 |
|
Nominal frequency |
Hz |
60 |
60 |
|
Maximum diameter of the insulating part |
mm |
98 |
98 |
|
Minimum creepage distance |
mm |
645 |
945 |
|
Minimum arcing distance |
mm |
210 |
285 |
|
Number of sheds |
No. |
6 |
9 |
|
Sheds diameter |
mm |
98 |
98 |
|
Passage of the sheds |
mm |
35 |
35 |
|
Sheds tilt angle |
° |
3 |
3 |
|
Withstand voltage at power frequency: | ||||
- Wet |
kV |
≥100 |
≥110 |
|
- Dry |
kV |
≥130 |
≥140 |
|
Impulse withstand voltage 1.2/50us: |
kV |
|||
- Positive |
kV |
≥190 |
≥240 |
|
Low Frequency Test Voltage (RMS to Earth) |
kV |
20 |
30 |
|
RIV Maximum at 1000 KHz |
µV |
10 |
10 |
|
6 |
Mechanical values: | |||
Specified Maximum Mechanical Load (SML) |
kN |
70 |
70 |
|
Specified Mechanical Test Load (RTL) |
kN |
35 |
35 |
|
Torque |
N-m |
47 |
47 |
|
Core diameter |
mm |
16 |
16 |
|
Weight |
kg |
1.4 |
1.9 |
|
7 |
Design Tests |
According to clause 10 IEC 61109 |
According to clause 10 IEC 61109 |
|
8 |
Type Tests |
According to clause 11 IEC 61109 |
According to clause 11 IEC 61109 |
|
9 |
Sampling tests |
According to clause 12 IEC 61109 |
According to clause 12 IEC 61109 |
|
10 |
Individual tests |
According to clause 13 IEC 61109 |
According to clause 13 IEC 61109 |
|
11 |
UV resistance tests |
According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 |
According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 |
Product detail pictures:
Related Product Guide:
Using a complete scientific high quality management program, superior high quality and superior faith, we acquire great reputation and occupied this industry for OEM Famous Self-supporting cable Pricelist – Suspension type Polymeric Insulator – Holley , The product will supply to all over the world, such as: Chile, Mauritania, Bandung, Our company, is always regarding quality as company' s foundation, seeking for development via high degree of credibility , abiding by iso9000 quality management standard strictly , creating top-ranking company by spirit of progress-marking honesty and optimism.