China OEM 2G module Pricelist –Self-Supporting Aluminum Cable– HolleyDetail:
Specifications
DESCRIPTION | UNIT | VALUE | VALUE | VALUE | VALUE | VALUE | |
1 | GENERAL |
| 3×35 + 1×16 + NA25 mm2 | 3×50 + 1×16 + NA35mm2 | 3×70 + 1×16 + NA50 mm2 | 3×25 + 1×16 + NA25 mm2 | 3X120 + 1X16 + NA70 mm2 |
| Manufacturing standard |
| NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 |
2 | DESIGNATION | CAAI | CAAI | CAAI | CAAI | CAAI | |
| Rated Voltage Uo / U | kV | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 |
3 | TERMS OF USE | ||||||
| Maximum temperature in permanent regime. | ° C | 90 | 90 | 90 | 90 | 90 |
| Maximum temperature in overload regime. | ° C | 130 | 130 | 130 | 130 | 130 |
| Maximum temperature in short-circuit mode (5 s) | ° C | 250 | 250 | 250 | 250 | 250 |
4 | CABLES GATHERING: | ||||||
| Maximum wireways, depending on the diameter of thePhase wire | Times | 60 | 60 | 60 | 60 | 60 |
5 | PHASE CABLE: | ||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | |
| Material | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated Aluminum | |
| Nominal section | mm2 | 35 | 50 | 70 | 25 | 120 |
| Class | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 7 | 6 | 12 | 6 | 15 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 0.868 | 0.641 | 0.443 | 1.20 | 0.253 |
| Insulation | ||||||
Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | ||
XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
Minimum average thickness | mm | 1.14 | 1.52 | 1.52 | 1.14 | 2.03 | |
Minimum thickness at one point | mm | 1.03 | 1.37 | 1.37 | 1.03 | 1.83 | |
6 | STREET LIGHT CABLE | ||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP 370.250 | |
| Material | Pure Aluminum without Coating | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | |
| Nominal section | mm2 | 16 | 16 | 16 | 16 | 16 |
| Class | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 7 | 6 | 6 | 6 | 6 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | |
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | |
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 |
| Minimum average thickness | mm | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 |
| Minimum thickness at one point | mm | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 |
7 | NEUTRAL CABLE SUPPORT | ||||||
Standards | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | ||
Cable Material | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | ||
Conductivity | % IACS | 52.5 | 52.5 | 52.5 | 52.5 | 52.5 | |
Nominal section | mm2 | 25 | 35 | 50 | 25 | 70 | |
Number of wires | 7 | 7 | 7 | 7 | 7 | ||
Wire diameter | mm | 2.13 | 2.52 | 3,023 | 2.13 | 3.57 | |
| Minimum tensile strength | kN | 7.72 | 10.81 | 15.44 | 7.72 | 20.95 |
| Nominal Mass | kg / km | 68.4 | 95.7 | 136.8 | 68.4 | 191.5 |
| Density at 20 ° C | kg / m3 | 2703 | 2703 | 2703 | 2703 | 2703 |
| Electrical resistivity at 20 ° C | Ωmm2 / m | 0.032840 | 0.032840 | 0.032840 | 0.032840 | 0.032840 |
| Maximum electrical resistance in DC at 20 ° C | Ω / km | 1.3511 | 0.9651 | 0.6755 | 1.3511 | 0.4825 |
| Insulation | ||||||
Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | ||
XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
Minimum average thickness | mm | 1.14 | 1.14 | 1.52 | 1.14 | 1.52 | |
Minimum thickness at one point | mm | 1.03 | 1.03 | 1.37 | 1.03 | 1.37 |
Product detail pictures:

Related Product Guide:
With our abundant experience and considerate products and services, we have been recognized to be a reputable supplier for a lot of global consumers forChina OEM 2G module Pricelist –Self-Supporting Aluminum Cable– Holley, The product will supply to all over the world, such as: Sydney, Nepal, US, To let customers be more confident in us and get the most comfortable service, we run our company with honesty, sincerity and best quality . We firmly believe that it is our pleasure to help customers to run their business more successfully, and that our professional advice and service can lead to more suitable choice for the customers.