Specifications
| Item | Sub-item | Parameter |
| Basic | Meter Type | 3 Phase 4 Wire |
| Meter Standard | ANSIC12.1, ANSIC12.10, ANSI C12.20, ANSIC12.16, ANSI C62.41, ANSI C37.90.1, ANSI C12.18, ANSI C12.19, ASTM -B117, UL-50 | |
| Active Accuracy | Active Class 0.2, Reactive Class 1 | |
| Rated voltage Un | 240V | |
| Operating Voltage Range | 0.7Un~1.15Un | |
| Operating frequency | 50HZ±5% | |
| Current | 16S: 30A(200A)/15(100A); 9S: 2.5A(20A) | |
| Starting current | 16S: 0.1A/0.05A; 9S: 0.01A | |
| Constant | 16S: KH2.5; 9S: KH2.0 | |
| Communication | Optical port | Protocol: ANSI C12.18/ANSI C12.19 |
| Measurement | Energy | Active energy, Reactive energy (leading), Reactive energy (lagging) |
| Instantaneous | Voltage, Current, Power factor, Active power, Reactive power | |
| Demand | Active maximum demand, Active cumulative demand, Instantaneous active demand | |
| TOU | Rates | Support up to 4 rates, rate period configurable |
| Billing | Billing time & day | Configurable, default 00:00 on the first day of each month |
Billing objects | Total kWh, Leading kVarh, Lagging kVarh, Active MD and time of occurrence, Active cumulative demand | |
Historical data | 40 historical data | |
| LED & LCD Display | LED | 1 active pulse indicator, 1 reactive pulse indicator, 1 tamper alarm indicator |
LCD digits | Total 7 digits, number of integers and decimals configurable | |
Display parameters | Configurable to show energy, demand, instantaneous values, etc. | |
Mode of display scroll | Auto scroll and manual scroll are available. Manual scroll is realized by magnet touch | |
Power off display | LCD can be turned on to show scroll parameters by magnet touch and will be off in 5 minutes | |
Battery | Backup battery | - Expected life 10 year - Replaceable |
RTC | Accuracy | ≤0.5s/day (in 23°C) |
Synchronization | By communication command | |
| Event | Event log | 300 events |
Main events | Power off/on, time change, demand reset, rate change, measurement error, low battery, reverse current | |
| Other | Enclosure protection | UL50 Type 3 |
This meter's three-phase, four-wire configuration is ideal for comprehensive energy consumption and production analysis in Grid-connected PV power stations. The socket-type design simplifies installation and maintenance, enabling seamless integration into existing infrastructures. By opting for the DTSD546, Grid-connected PV power stations can rely on its state-of-the-art static TOU (Time of Use) technology, which allows operators to adjust and adapt energy usage according to real-time needs and tariffs, thus maximizing the financial and operational benefits of solar energy integration. Holley's DTSD546 is more than just a meter; it serves as an essential component in the optimization of Grid-connected PV power station operations. Its precision and reliability contribute significantly to enhancing the efficiency and sustainability of solar energy projects. By ensuring accurate measurement and monitoring, this meter assists in seamlessly integrating renewable energy sources into national and local grids, paving the way for a greener, more sustainable future. With Holley's commitment to innovation and quality, the DTSD546 is the top choice for those prioritizing performance and precision in their solar energy initiatives.