OEM Famous Prime module Quotes –Medium Voltage Copper Cable– HolleyDetail:
Specifications
DESCRIPTION | UNIT | VALUE | VALUE | VALUE | VALUE | VALUE | VALUE | VALUE | |
1 | GENERAL |
| 1X70mm2 8.7 / 15 (17.5) kV | 1x120mm2, 8.7 / 15 (17.5) kV | 1×150 mm2, 8.7 / 15 (17.5) kV | 1x70mm2, 18/30 (36) kV | 1X120mm2 FOR 18/30 (36) kV | 1×185 mm2, 8.7 / 15 (17.5) kV | 1X185mm2 FOR 18/30 (36) kV |
| Standard |
| NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 | NTP IEC 60502-2 |
2 | DESIGNATION N2XSY | 1 x 70 mm2 | 1 x 120 mm2 | 1 x 150 mm2 | 1 x 70 mm2 | 1 x 120 mm2 | 1 x 185 mm2 | 1 x 185 mm2 | |
| Rated Voltage Uo / U (Uo) | kV | 8.7 / 15 (17.5) | 8.7 / 15 (17.5) | 8.7 / 15 (17.5) | 18/30 (36) | 18/30 (36) | 8.7 / 15 (17.5) | 18/30 (36) |
| Maximum temperature under normal conditions | ° C | 90 | 90 | 90 | 90 | 90 | 90 | 90 |
| Maximum short-circuit temperature (5 s. Maximum) | ° C | 250 | 250 | 250 | 250 | 250 | 250 | 250 |
3 | PHASE CONDUCTOR | ||||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | |
| Material | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | Uncoated Annealed Copper | |
| Purity | % | 99.9 | 99.9 | 99.9 | 99.9 | 99.9 | 99.9 | 99.9 |
| Nominal section | mm2 | 70 | 120 | 150 | 70 | 120 | 185 | 185 |
| Class | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 19 | 37 | 37 | 19 | 37 | 37 | 37 |
| Density at 20 ° C | gr / cm3 | 8.89 | 8.89 | 8.89 | 8.89 | 8.89 | 8.89 | 8.89 |
| Electrical resistivity at 20 ° C | Wmm2 / m | 0.017241 | 0.017241 | 0.017241 | 0.017241 | 0.017241 | 0.017241 | 0.017241 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 0.268 | 0.153 | 0.124 | 0.268 | 0.153 | 0.099 | 0.099 |
| Insulation | ||||||||
| Material | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | XLPE-TR (Tree Retardant Cross-linked Polyethylene) | ||
| Colour | natural | natural | natural | natural | natural | natural | natural | ||
| Average nominal thickness | mm | 4.5 | 4.5 | 4.5 | 8 | 8 | 4.5 | 8 | |
| Screen |
|
|
|
|
|
|
|
|
| Semiconductor tape or extruded compound semiconductor on the conductor | YES | YES | YES | YES | YES | YES | YES | ||
| About the insulator | |||||||||
| Semiconductor tape or extruded composite semiconductor | YES | YES | YES | YES | YES | YES | YES | ||
| Copper wire braided mesh or tape with resistance less than 3 ohm/km at 20 ° C |
| YES | YES | YES | YES | YES | YES | YES |
| Sheath | |||||||||
| Material | PVC –ST2 | PVC – ST2 | PVC – ST2 | PVC –ST2 | PVC – ST2 | PVC – ST2 | PVC – ST2 | ||
| Colour | Red | Red | Red | Red | Red | Red | Red | ||
| Minimal thickness | mm | 1.2 | 1.2 | 1.3 | 1.4 | 1.5 | 1.4 | 1.6 | |
| Tests |
|
|
|
|
|
|
|
|
| Insulation Continuity Test Voltage | kV | 30.5 | 30.5 | 30.5 | 63 | 63 | 30.5 | 63 | |
| Insulation construction process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process | Through simultaneous triple extrusion process |
Product detail pictures:

Related Product Guide:
We can normally fulfill our respected consumers with our great excellent, great value and good provider due to we're much more specialist and extra hard-working and do it in cost-effective way forOEM Famous Prime module Quotes –Medium Voltage Copper Cable– Holley, The product will supply to all over the world, such as: Singapore, Germany, Guinea, Should any of these items be of interest to you, please let us know. We'll be satisfied to give you a quotation upon receipt of one's detailed specifications. We have our personal experienced R&D enginners to meet any of one's requriements, We appear forward to receiving your enquires soon'and hope to have the opportunity to work together with you in the future. Welcome to check out our company.